BLX Engineering Tool: LinkIO

RSS
Modified on 2023/05/17 09:25 by MKR Categorized as QCX BlendExpert Mill V8
PointPoint TypeDirectionExplanationUnitRange
.IOAutomaticdigitalread from PLCIndicates if BLX set-points are employed or notautomatic / manualn/a
.SPTotalanalogread from PLCSet-point for total feed to millt/hr0 - max capacity
.IOReadyDoublewrite to PLCIndicates if BLX has no errorson / offn/a
.IOOKDoublewrite to PLCIndicates to CCR that BLX is ready and selected in Labon / offn/a
.IOHeartbeatDoublewrite to PLCIndicates to plant control system that BLX is alive at 10 seconds intervalson / offn/a
.PVanalogread from PLCFeeders process value (one PV for each feeder)t/hrminimum capacity of feeder - max capacity of feeder
.STSdigitalread from PLCFeeders run / stop statusrun / stopn/a
.SELdigitalread from PLCFeeder selection indicates to BLX if a feeder is available or noton / offn/a
.SPanalogwrite to PLCBLX feeder set-point%0 - 100%
.WSPanalogread from PLCFeeders working set-point; from BLX or operator%0 - 100%
.STSDigitalread from PLCMill start stopon / offN/A



Example of list of points for BLX which can se sent to the client at site. The origianal file can be found under the BLX super user Teamssite.]



 