How to accept negative values from an analyser
Modified on 2022/05/24 13:40
by
MKR
Categorized as
How to
,
QCX BlendExpert Mill V8
,
QCX V8
It can often happen that for instance an Online Analyser gives negative values and this can cause the sample to be rejected and then BLX will not do new set points. [image:{UP(How-to-accept-negative-values-from-an-analyser)}NegativeValues_2.png|medium] To prevent this the Lower limit can be removed in the QCX Lab Editor - DataItem list. [image:{UP(How-to-accept-negative-values-from-an-analyser)}NegativeValues_1.png|medium] Here on the image the Lower Limit for MgO have been removed and now all analysis with negative values are accecpted by QCX. [image:{UP(How-to-accept-negative-values-from-an-analyser)}NegativeValues_3.png|medium]