BLX V8 Adding an Online Analyser |
Date: | 18/01/2019 |
Author: | Mette Katrine Runge |
Who can use this': | FLSA Engineers with some XML copy/paste, search/replace capabilities |
Notes': | Only supports addition of Online Analyser to an already installed BLX. You need the original BLX engineering excel spreadsheet to build new solutions including the Online analyser Time estimate 1 hour. If this guide is followed |
Support files': | Can be found on the BLX Super user site. The zip files contains an example of the solutions files ready for import into QCX after finished editing. Also is a recording of Torsten showing the procedures |
This info can also be found on the BLX Super User site
Step by Step
- Make a backup of configuration and runtime databases… in the unlike event of something goes bad
- Create new BLX engineering file based on the original file and including the new Online Analyser and the preferred configuration.
- Use BLX Builder to create new solution files
- The following files needs to edited (see also link above to example of files):
- Specific Solution:
- Fls.Core.Config.Solution.xml
- Fls.Core.Ref.xml
- Fls.QcxBlx.Mill.Config.xml
- HMI Solution
- Fls.Core.Config.Solution
- Fls.Core.Hmi
- Folder: Fls.Core.Hmi
- Delete all EXCEPT the three files defining the online.
- In each file delete everything not related to the Online Sampler as described in the following table:
File | Delete |
Specific solution: Fls.Core.Config.Solution.xxml | Noting to delete here Make sure naming is correct on Designation solution and sourceName. Check QCX configuration in: Core.Config.Solution |
Specific solution: Fls.Core.Ref.xml | Remember to keep the original roote down to the info on the Online Analyser – see example Else delete all not related to the online sampler. |
Specific solution: Fls.QCX.Blx.Config.xml | Delete all sections NOT related to the Online Analyser. Remember to delete the three lines called: successorSubsection related to the online sampler. Can be found towards the end of the file. Do a search. |
HMI Solution: Fls.Core.Hmi | Under Mimics: delete all files NOT related to the Online Analyser |
HMI solution: Fls.Core.Hmi.xml | Delete everyting NOT related to the online analyser |
Transfer the files to the system
Import the solutions folders to QCX
- Ensure the files are in the original solutions – have right solution names!
- In Config – Config – Blx – Plantsection add the online to the list of subsections by adding a new line and selection the Online.
- In Config – Config – Blx – Subsection change successorSubsections to right order for example: Merger delay 1 online mill lab …..
- Edit the HMI and add the online mimics in the Matric.